V-BANK HIGH CAPACITY HEPA FILTER
292mm

 

V-BANK HIGH CAPACITY HEPA FILTER-292mm
Testing Standard
D.O.P.
 
99.999%
 
 
 
Testing
99.99%
at
0.3
μm
P.S.L.
 
99.97%
 
 
Character

  1. Mini-pleated V-Bank Air Filter(Thickness 292mm)
  2. High-capacity Low P.D.
  3. EN 1822 Class H11/H12/H13/H14
  4. IES RP-CC-001.3 TYPE A/B/C/D
  5. Long Service Life
  6. Energy Saving
Application

  1. Air Conditioner(AHU,MAU,RAU)
  2. Desinfection Chamber(ICR,BCR)CLASS 10~10K
  3. FILTER UNIT,AIR SHOWER,CLEAN BENCH,CLEAN BOOTH
Operating Condition

  1. Max Operating Temperature : 80℃
  2. Max Humidity : 100%RH(Non-Foggy)
Produced Environment Produced in desinfection chamber at CLASS 1000 degree

PERFORMANCE AND OPERATING CONDITIONS

MODEL OUTSIDE DIMENSION(mm) m³/min CFM INITIAL P.D. FINAL P.D.
L W D
Box ※-HEPA-VK-
L X W X H(D)-H-BOX
305 610 292 28 1000 249 Pa
(25.4 mmH2O)
500 Pa
(50.8 mmH2O)
610 610 292 56 2000
Flange ※-HEPA-VK-
L X W X H(D)-H-F
288 593 292 24 1000 270 Pa
(27.7 mmH2O)
593 593 292 52 2000
※=Frame(Aluminum(U)、Glvanized Iron(D)、Stainless Steel(S))
(Special size available upon request)

 

MATERIALS

MODEL U-HEPA-VK-H D-HEPA-VK-H S-HEPA-VK-H
Material FRAME ANODIZE ALUMINUM ANODIZE ALUMINUM SUS 304
MEDIA MICRO GLASS FIBER MICRO GLASS FIBER MICRO GLASS FIBER
SEALANT SYNTHEIC RESIN SYNTHEIC RESIN SYNTHEIC RESIN
GASKET NEOPRENE NEOPRENE NEOPRENE

 

Performace & Operating Condition

ITEM INTIAL P.D.
Wind Velocity 1.56m/sec 140 Pa
(14.3mmH2O)
2.77m/sec 249 Pa
(25.4mmH2O)
Operating Condition MAX TEMPERATURE 60℃
MAX HUMIDITY 100% RH

 

Initial P.D.

 